Power factor correction kVAr

Power factor correction kVAr: Required capacitor kVAr = kW × (tan acos(old PF) − tan acos(target PF)).

Make it your own ⌁ Runs on your device

Your inputs are processed locally and are not added to analytics or saved history.

YOUR RESULT
Ready when you are.

Enter your values, then select Calculate.

How it works

Required capacitor kVAr = kW × (tan acos(old PF) − tan acos(target PF)).

Input definitions

Real power (kW)
Enter the value in the labeled unit.
Existing power factor
Enter the value in the labeled unit.
Target power factor
Enter the value in the labeled unit.

A worked example

Real power (kW)
100
Existing power factor
0.75
Target power factor
0.95
55.3233

Assumptions & limits

Uses only the values entered. Rates are illustrative inputs, not live quotes, legal rules or personalised advice. Check provider terms, local requirements and measurements before acting.

Sources & review

Maintained by AnsRio. Methods and examples use automated checks; this does not imply independent professional certification.

Method updated 2026-10-19. Content checked against the stated method and examples. Our verification approach.

Report an issue with this tool or suggest an improvement ↗

Common questions

Is this enough to specify a capacitor bank?

No. Harmonics, switching steps, voltage, resonance and utility requirements need engineering review.

How does Power factor correction kVAr calculate the result?

Required capacitor kVAr = kW × (tan acos(old PF) − tan acos(target PF)).

What should I verify before using Power factor correction kVAr?

Uses only the values entered. Rates are illustrative inputs, not live quotes, legal rules or personalised advice. Check provider terms, local requirements and measurements before acting.

↗